Configuring the system
2.1 System settings
PCU-Basesoftware (IM8)
34
Commissioning Manual, 03/2009, 6FC5397-1DP10-4BA0
2.1.2
How to set the IP address of the PCU 50.3
Default
NOTICE
The IP address 192.168.214.241 is set as a factory default for every PCU 50.3 on the
system network.
You must only perform the steps described below if you wish to change this default.
Procedure
1.
Select the following on the PCU on the service desktop: "Start" → "Settings" → "Network
Connections".
The "Network Connections" window opens.
2.
Double-click the Ethernet 2 interface you want to parameterize which is to be used for
connecting the TCU or system network.
The "Ethernet 2 (System Network) Properties" window opens.
3.
Under the "General" tab, select "Internet Protocol (TCP/IP)" and click the "Properties"
button.
The "Internet Protocol (TCP/IP) Properties" window opens: