Parameterizing machine data
3.2 Parameterizing the control using machine data
HMI Advanced (IM4)
Commissioning Manual, 03/2009, 6FC5397-0DP10-3BA0
111
Example: In the diagram, the measured power is 10.5 kW.
Figure 3-6
Servo trace: Evaluation
If the utilization display is to indicate 100% for nominal data and higher values at operation
above the nominal working point, the normalization factor setting can be calculated from the
motor data or from the diagram and measurement as follows:
MA_SPIND_MAX_POWER = Maximum_of_the_measured_power / rated power_S1 * 100
MA_SPIND_MAX_POWER = 10500W / 7000W * 100 = 150
Enter the factor 150 in the machine data.