Reaction:
NC not ready.
Mode group not ready, also effective for single axes.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Please inform the authorized personnel/service department. 3 MD identifiers are output, depending on the type of error.
1. MD30500 $MA_INDEX_AX_ASSIGN_POS_TAB: the error is due to multiple assignment of a position table MD10910
$MN_INDEX_AX_POS_TAB_1 or MD10930 $MN_INDEX_AX_POS_TAB_2) to axes with different types (linear/rotary axis).
2. MD10910 $MN_INDEX_AX_POS_TAB_1 or MD10930 $MN_INDEX_AX_POS_TAB_2: the contents of the displayed
tables are incorrect.
- The entered positions must be arranged in increasing size.
- A particular position must not be set more than once.
- If the table is assigned to one or several modulo axes, then the contents must be within the 0 to < 360 degree range.
3. MD10900 $MN_INDEX_AX_LENGTH_POS_TAB_1 or MD10920 $MN_INDEX_AX_LENGTH_POS_TAB_2: the length
of the displayed position table n was specified with 0.
Programm
continuation:
Clear alarm with the RESET key. Restart part program
4082
[channel %1: ] invalid value in machine date %2%3
Parameters:
%1 = Channel number
%2 = String: MD identifier
%3 = String: MD field index
Explanation:
A value has been entered which exceeds the value range or a limit value for a variable, a machine data or a function.
Reaction:
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Enter correct values.
Programm
continuation:
Clear alarm with the RESET key. Restart part program
4090
Too many errors during power-up
Explanation:
More than <n> errors occurred during control power-up.
Reaction:
NC Start disable in this channel.
Alarm display.
Remedy:
Set the machine data correctly.
Programm
continuation:
Switch control OFF - ON.
4110
IPO cycle changed to %1 ms
Parameters:
%1 = String (new IPO cycle time)
Explanation:
The IPO cycle divisor was set to a value which was not an integral multiple of the position control cycle divisor. The divisor
(MD10070 $MN_IPO_SYSCLOCK_TIME_RATIO) was increased.
For PROFIBUS/PROFINET: MD10070 $MN_IPO_SYSCLOCK_TIME_RATIO has been modified because of the modified
DP cycle in the SDB (MD10050 $MN_SYSCLOCK_CYCLE_TIME).
Reaction:
Alarm display.
Remedy:
MD10070 $MN_IPO_SYSCLOCK_TIME_RATIO has been modified.
Programm
continuation:
Clear alarm with the RESET key. Restart part program
SINUMERIK 808D ADVANCED alarms
5.2 NCK alarms
Diagnostics Manual
60
Diagnostics Manual, 06/2015, 6FC5398-6DP10-0BA2