Remedy:
The address partitioning should be checked as follows:
Check for multiple assignments in the following machine data:
- MD13050 $MN_DRIVE_LOGIC_ADDRESS[0] - MD13050 $MN_DRIVE_LOGIC_ADDRESS[n-1] : n = highest axis index
on control system
- MD12970 $MN_PLC_DIG_IN_LOGIC_ADDRESS, MD12971 $MN_PLC_DIG_IN_NUM : PLC address area for digital
inputs
- MD12978 $MN_PLC_ANA_IN_LOGIC_ADDRESS, MD12979 $MN_PLC_ANA_IN_NUM : PLC address area for analog
inputs
If no inconsistencies can be found in the parameters, compare these machine data with the configuration in SDB (STEP
7 project). In particular, check that the lengths configured for the individual slots do not result in area overlaps. When you
find the cause of the error, change the machine data and/or SDB.
Programm
continuation:
Switch control OFF - ON.
380051
PROFIBUS/PROFINET: Multiple assignment of outputs on address %1
Parameters:
%1 = Logical address
Explanation:
Multiple assignments of input data have been detected in the logical address space. Logical address: Base address of the
address area defined several times
Reaction:
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
The address partitioning should be checked as follows:
Check for multiple assignments in the following machine data:
- MD13050 $MN_DRIVE_LOGIC_ADDRESS[0] - MD13050 $MN_DRIVE_LOGIC_ADDRESS [n-1] : n = highest axis index
on control system
- MD12974 $MN_PLC_DIG_OUT_LOGIC_ADDRESS, MD12975 $MN_PLC_DIG_OUT_NUM : PLC address area for
digital outputs
- MD12982 $MN_PLC_ANA_OUT_LOGIC_ADDRESS, MD12983 $MN_PLC_ANA_OUT_NUM : PLC address area for
analog outputs
If no inconsistencies can be found in the parameters, compare these machine data with the configuration in the SDB (STEP
7 project). In particular, check that the lengths configured for the individual slots do not result in area overlaps. When you
find the cause of the error, change the machine data and/or SDB.
Programm
continuation:
Switch control OFF - ON.
380060
PROFIBUS/PROFINET: Alarm %1 on logical address %2 from unassigned slave/device
Parameters:
%1 = Alarm class
%2 = Logical address
Explanation:
SDB contains a slave/device which is not assigned in the NC via the MD parameters (see also alarm 380050/051). The
slave/device is however connected to the PROFIBUS/PROFINET, and has reported an alarm.
Alarm class:
- 01 = Station return (or arrival)
- 02 = Station failure
Display alarm, further operation with the NC is possible.
Reaction:
Alarm display.
Remedy:
- Enter machine data or
- Modify SDB or
- Disconnect the slave/device from the PROFIBUS/PROFINET or
- Acknowledge the alarm.
Programm
continuation:
Clear alarm with the Delete key or NC START.