400032
System error, the project cannot run on this PLC version
Explanation:
The project comprises instructions which are not known in this PLC version
Reaction:
PLC Stop
Remedy:
Load original project.
Programm
continuation:
Clear alarm with the Delete key or NC START.
400033
Permissible number of commands exceeded: %2 Network %1
Explanation:
Permissible number of commands exceeded
%1 : Network number
%2 : Current number of commands, block
Reaction:
PLC Stop
Remedy:
The user project comprises too many commands, shorten user project or activate the option number of commands
Programm
continuation:
Clear alarm with the Delete key or NC START.
5.6
PLC user alarms
700000 to 700127
PLC User alarms
For the default PLC program, refer to descriptions of PLC subroutines in the
Commissioning Manual
for detailed information about the PLC user alarms.
For an machine manufacturer PLC program, refer to relevant descriptions of machine tool for detailed
information about the PLC user alarms
SINUMERIK 808D ADVANCED alarms
5.6 PLC user alarms
Diagnostics Manual
Diagnostics Manual, 06/2015, 6FC5398-6DP10-0BA2