Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Please inform the authorized personnel/service department. Do not use rapid interrupt inputs or contact the machine
manufacturer with a view to retrofitting this option!
Programm
continuation:
Clear alarm with the RESET key. Restart part program
8010
Option 'activation of more than %1 axes' not set
Parameters:
%1 = Number of axes
Explanation:
More machine axes have been defined through the MD20070 $MC_AXCONF_MACHAX_USED than are allowed in the
system.
Reaction:
NC not ready.
Mode group not ready, also effective for single axes.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Please inform the authorized personnel/service department.
The sum of all axes that have been configured using the channel-specific MD20070 $MC_AXCONF_MACHAX_USED
must not exceed the maximum number of axes.
Reduce the number of active axes or enable additional axes via option.
Please also observe the information relating to the definition of auxiliary axes/spindles.
Programm
continuation:
Switch control OFF - ON.
8012
The 'Activation of more than %1 SI axes' option is not set
Parameters:
%1 = Number of licensed axes
%2 = Number of axes with active dbSi
Explanation:
The drive-based safety functions were activated for more axes than permitted in the system.
Reaction:
NC not ready.
Mode group not ready, also effective for single axes.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Please notify the authorized personnel / service department. Reduce the number of axes activated with drive-based safety
functions or release additional axes in the option date.
Programm
continuation:
Switch control OFF - ON.
8022
Option 'activation of more than %1KB SRAM' not set
Parameters:
%1 = Memory size
Explanation:
The option for memory extension does not correspond to the active SRAM.
Reaction:
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Please inform the authorized personnel/service department.
- Buy option
- Activate less SRAM
SINUMERIK 808D ADVANCED alarms
5.2 NCK alarms
Diagnostics Manual
88
Diagnostics Manual, 06/2015, 6FC5398-6DP10-0BA2