Opti-Core
®
Push-Pull LC Duplex
Fiber Optic Patch Cords
S P E C I F I C A T I O N S H E E T
c o n s t r u c t i o n
Fiber count:
Duplex (2-fiber) jacketed zipcord
Cable jacket
ratings:
Riser (OFNR)
Low Smoke Zero Halogen
(LSZH) per: IEC 60332-1-2,
IEC 60332-3-24, IEC 60754-1,
IEC 60754-2, IEC 61034-2
Fiber types:
Singlemode: OS1/OS2 9/125µm
Multimode: OM3 50/125µm
OM4 50/125µm
Connector types,
End ‘A’:
Duplex LC
Connector types,
End ‘B’:
Duplex LC
Jacket color:
OS1/OS2: Yellow
OM3: Aqua
OM4: Aqua
a p p l i c a t i o n
Provide interconnect and cross-connect of applications in entrance facilities, telecommunication rooms, data centers, at the
desk and network applications to interconnect pre-terminated cassettes in main distribution, horizontal distribution, and
equipment distribution areas.
t e c h n i c a l i n f o r m a t i o n
Push-Pull LC Duplex Fiber Optic Patch Cords containing the custom push-pull strain
relief boot and duplex clip, allow users easy accessibility when deploying very high
density LC patch fields in data center applications. Available in riser (OFNR), and low
smoke zero halogen (LSZH) rated jacket materials to comply with local cabling
ordinances and OM4, OM3 or OS1/OS2 fiber types to meet the demands of today's
highest speed applications.
p h y s i c a l p r o p e r t i e s
Cable outside diameter (OD):
1.6mm duplex
Bend Radius (min) Short-Term:
16mm
Bend Radius (min) Long-Term:
32mm
Connector cable retention:
50N (4.24lb) @ 0°
19.4N (4.4lb)@ 90°
Connector durability:
500 cycles
e n v i r o n m e n t a l p r o p e r t i e s
Storage and
wshipping temperature:
-40°C to 70°C
Operating and
installation temperature:
-10°C to 60°C
www.panduit.com
o p t i c a l p r o p e r t i e s
Connector
insertion loss:
Standard: 0.25dB max (OM3 and OM4)
0.35dB max (OS2)
Optimized: 0.15dB max (OM3 and OM4)
Ultra: 0.10dB max (OM4)
Connector
return loss:
26dB min (OM3 and OM4)
55dB min (OS1/OS2)
s t a n d a r d s
Meets or exceeds ISO/IEC 11801, TIA-568-C.3,
TIA-604-10 (FOCIS-10)
Restriction of Hazardous
Substances (RoHS) Compliance:
All patch cord
components meet
the requirement
of Directive
2002/95/EC