251
F3SG-SR/PG
User’s Manual
Chapter
4
Cha
nging Set
tings
with SD
Ma
nag
e
r 3
Setting with SD Manager 3
E
If using this function together with other functions, make settings taking the condition of adjacent zones into account.
For more information on zone adjacency conditions, refer to
2-19. Setting Zone Adjacency Conditions
.
When changing the settings is complete, confirm the settings and write the configuration to the F3SG-SR/PG.
To enable the written configuration, refer to
4-2-7-3. Writing Configuration into Intelligent Tap
When connecting the Intelligent Tap to a F3SG-SR/PG and trying to return the F3SG-SR/PG to [Detecting], follow step 4
of
4-1-3-2. Connection Procedure When Using USB Connector
to restart the F3SG-SR/PG and Intelligent Tap, or click
the [Monitor]
button.
No.
Function name
Description
Initial
value
Configurable value or
numerical range
1
Muting Time
Information
Enter values of Muting-related time limits.
For the Muting time input time limit and the Muting time limit,
setting the value to zero means the time limit is infinite.
-
-
Standard muting
T1min: Muting input time limit
(Min. value)
0.1 s
0.1 to 3.9 s (in 0.1 s
increments)
T1max: Muting input time limit
(Max. value)
4 s
0.2 to 60 s (in 0.1 s
increments)/infinite
T2: Muting time limit
60 s
1 to 600 s (in 1 s
increments)/infinite
T3: Maximum allowable
muting signal interruption
0.1 s
0.1 to 20 s (in 0.1 s
increments)
Exit-only muting
T1min: Muting input time limit
(Min. value)
0.1 s
0.1 to 3.9 s (in 0.1 s
increments)
T1max: Muting input time limit
(Max. value)
4 s
0.2 to 600 s (in 0.1 s
increments)/infinite
T2: Muting time limit
60 s
1 to 600 s (in 1 s
increments)/infinite
T3: Maximum allowable
muting signal interruption
0.1 s
0.1 to 4 s (in 0.1 s
increments)
T4: Muting end waiting time
1 s
0.1 to 20 s (in 0.1 s
increments)
T5: Exit-only muting delay time
4 s
4 to 20 s (in 0.1 s
increments)
Position detection muting
T1max: Muting input time limit
(Max. value)
4 s
0.2 to 60 s (in 0.1 s
increments)/infinite
T2: Muting time limit
60 s
1 to 600 s (in 1 s
increments)/infinite
T3: Maximum allowable
muting signal interruption
0.1 s
0.1 to 4 s (in 0.1 s
increments)
2
Check installation
position
Reflects the Muting Time Information settings to the timing
chart shown in the left side of the screen, and allows data entry
to the Input Information fields.
-
-
3
Input Information
Enter information about the work-piece.
-
-
4
Diagnosis of
installation
condition
It is diagnosed and displayed if the setting condition is
appropriate.
-
-
5
Evaluate
Checks if the muting with the entered settings is possible.
-
-
6
Installation
diagram and
Timing chart
Shows the positions and timing chart of a work-piece, the
F3SG-SR/PG and muting sensors. You can also make settings
to the muting time information by editing the values in the
timing chart directly.
-
-
7
Close
Finishes the setting process of muting time information, and
returns to muting setting.
-
-
Summary of Contents for F3SG-PG Series
Page 18: ...xvi Introduction F3SG SR PG User s Manual...
Page 30: ...xxviii Introduction F3SG SR PG User s Manual...
Page 74: ...44 Chapter 1 List of Models F3SG SR PG User s Manual Overview and Specifications...
Page 180: ...150 Chapter 2 IO Link F3SG SR PG User s Manual System Operation and Functions...
Page 438: ...408 Chapter 7 Maintenance Checklists F3SG SR PG User s Manual Checklists...