![background image](http://html1.mh-extra.com/html/omron/f3sg-pg-series/f3sg-pg-series_user-manual_741299153.webp)
123
F3SG-SR/PG
User’s Manual
Chapter
2
Warn
in
g Zone
System Operation and Functions
E
You can specify beams to configure for warning zone. (Fig. 4& 5)
Configuration cannot be executed for cases shown below.
• All beams are configured as a warning zone (Fig. 7).
• A warning zone is configured without including either the top end beam or bottom end beam. (Fig. 8)
When it is configured for the F3SG-SR in cascade connection to have the detection zone, it is possible
for the other F3SG-SR's to have the warning zone for the all beams. (Fig. 6)
For the application as shown in Fig. 6, make sure the primary sensor has the detection zone and the secondary sensor
has the warning zone.
Operation Example
Timing chart
Warning Zone
Detection Zone
Fig. 1
Fig. 2
Fig. 3
Safety output ON
Warning zone output OFF
Safety output ON
Warning zone output ON
Safety output OFF
Warning zone output OFF
Beam state
(
W
arning zone only)
Beam state
(Detection zone)
Un
b
locked
Blocked
AUX
(
w
arning zone)
ON
OFF
Un
b
locked
Blocked
OSSD
ON
OFF
Summary of Contents for F3SG-PG Series
Page 18: ...xvi Introduction F3SG SR PG User s Manual...
Page 30: ...xxviii Introduction F3SG SR PG User s Manual...
Page 74: ...44 Chapter 1 List of Models F3SG SR PG User s Manual Overview and Specifications...
Page 180: ...150 Chapter 2 IO Link F3SG SR PG User s Manual System Operation and Functions...
Page 438: ...408 Chapter 7 Maintenance Checklists F3SG SR PG User s Manual Checklists...