F3SG-SR/PG
User’s Manual
System Operation and Functions
Standard Muting mode
Exit-Only Muting mode
Position Detection Muting mode
Dynamic Muting
It is recommended that the Position 2 of the DIP Switch be set at OFF (DIP Switch Disabled).
Setting the muting time limit to infinite may cause a failure of the muting sensors to go undetected, resulting in the F3SG-SR
in an unintended MUTING state. Conduct risk assessment analysis thoroughly before enabling this setting.
Setting the muting input time limit value (maximum) to infinite may cause a failure of the muting sensors to go
undetected, resulting in a failure of disabling the MUTING state. Conduct risk assessment analysis thoroughly before
enabling this setting.
Dynamic Muting can be used in conjunction with any of Standard, Exit-Only and Position Detection Muting modes.
Refer to
for more information on setting this function by the SD Manager 3.
Function
Initial value
Configurable value or numerical range
Muting zone
Bottom beam
All beams
any beam in 1-beam increments
Top beam
T1
min
: Muting input time limit value (minimum)
0.1 s
0.1 to 3.9 s in 0.1-s increments
T1
max
: Muting input time limit value (maximum)
4 s
0.2 to 60 s in 0.1-s increments, or infinite
T2: Muting time limit
60 s
1 to 600 s in 1-s increments, or infinite
T3: Maximum allowable muting signal interruption
0.1 s
0.1 to 20 s in 0.1-s increments
Function
Initial value
Configurable value or numerical range
Muting zone
Bottom beam
All beams
any beam in 1-beam increments
Top beam
T1
min
: Muting input time limit value (minimum)
0.1 s
0.1 to 3.9 s in 0.1-s increments
T1
max
: Muting input time limit value (maximum)
4 s
0.2 to 4 s in 0.1-s increments, or infinite
T2: Muting time limit
60 s
1 to 600 s in 1-s increments, or infinite
T3: Maximum allowable muting signal interruption
0.1 s
0.1 to 4 s in 0.1-s increments
T4: Muting end wait time
1 s
0.1 to 20 s in 0.1-s increments
T5: Exit-only muting delay time
4 s
4 to 20 s in 0.1-s increments
Function
Initial value
Configurable value or numerical range
Muting zone
Bottom beam
All beams
any beam in 1-beam increments
Top beam
T1
max
: Muting input time limit value(maximum)
4 s
0.2 to 60 s in 0.1-s increments, or infinite
T2: Muting time limit
60 s
1 to 600 s in 1-s increments, or infinite
T3: Maximum allowable muting signal interruption
0.1 s
0.1 to 4 s in 0.1-s increments
Function
Initial value
Configurable value or numerical range
Dynamic muting
Disable
Enable/Disable
Dynamic muting measurement time
3 s
1 to 25 s in 0.1-s increments
Number of dynamic muting allowable beams
1
0 to 5 in 1-beam increments
Summary of Contents for F3SG-PG Series
Page 18: ...xvi Introduction F3SG SR PG User s Manual...
Page 30: ...xxviii Introduction F3SG SR PG User s Manual...
Page 74: ...44 Chapter 1 List of Models F3SG SR PG User s Manual Overview and Specifications...
Page 180: ...150 Chapter 2 IO Link F3SG SR PG User s Manual System Operation and Functions...
Page 438: ...408 Chapter 7 Maintenance Checklists F3SG SR PG User s Manual Checklists...