F3SG-SR/PG
User’s Manual
Setting with SD Manager 3
When the optimization result below is obtained as a result of the flowchart above, there is a big
difference between T1 Max and A.D. Max, and between T1 Min and A.D. Min.shown in the chart below.
Now, change the T1 Min and T1 Max settings to 0.5 s and 1.0-1.2 s on the muting time information
setting screen.
8.
When setup is completed, execute writing into F3SG-SR/PG.
The deviation of T1 Min and Max from the A.D. Min and Max has been reduced, resulting in improved
safety, as shown below.
For more information on muting time information settings, refer to
.