Total output of
rotary servo
motors
Total
continuous
thrust of linear
servo motors
Total output of
direct drive
motors
Molded-case circuit breaker
(Note 4, 5)
Fuse
(Note 2)
Magnetic
contactor
Frame, rated current
Voltage
AC
[V]
(Note 1)
Class
Current
[A]
Voltage
AC
[V]
450 W or less
150 N or less
50 A frame 10 A
(Note 3)
240 T
20
300
S-N10
S-T10
From over 450
W to 800 W
From over 150
N to 300 N
252 W or less
50 A frame 15 A
(Note 3)
20
From over 800
W to 1.5 kW
From over 300
N to 450 N
From over 252
W to 378 W
50 A frame 20 A
(Note 3)
30
S-N20
S-T21
Note 1. When using the servo amplifier as an EC/EN/UL/CSA standard compliant product, refer to appendix 4.
2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until
closure of contacts) of 80 ms or less.
3. When not using the servo amplifier as an EC/EN/UL/CSA standard compliant product, molded-case circuit breaker
of 30 A frame can be used.
4.
A molded-case circuit breaker will not change to select regardless of use of a power factor improving AC reactor.
5. Use a molded-case circuit breaker which has the same or more operation characteristics than our lineup.
(2) For control circuit power supply
When the wiring for the control circuit power supply (L11, L21) is thinner than that for the main circuit
power supply (L1, L2, L3), install an overcurrent protection device (molded-case circuit breaker or fuse)
to protect the branch circuit.
Servo amplifier
Molded-case circuit breaker
Fuse (Class T)
Fuse (Class K5)
Frame, rated current
Voltage AC
[V]
Current [A]
Voltage AC
[V]
Current [A]
Voltage AC
[V]
MR-J4W2-22B
MR-J4W2-44B
MR-J4W2-77B
50 A frame 5 A (Note)
240
1
300
1
250
MR-J4W2-1010B
MR-J4W3-222B
MR-J4W3-444B
Note. When not using the servo amplifier as an EC/EN/UL/CSA standard compliant product, molded-case circuit breaker of
30 A frame can be used.
Summary of Contents for MR-J4W2
Page 9: ...A 8 MEMO ...
Page 17: ...8 MEMO ...
Page 31: ...1 FUNCTIONS AND CONFIGURATION 1 14 MEMO ...
Page 95: ...4 STARTUP 4 20 MEMO ...
Page 169: ...6 NORMAL GAIN ADJUSTMENT 6 20 MEMO ...
Page 201: ...7 SPECIAL ADJUSTMENT FUNCTIONS 7 32 MEMO ...
Page 213: ...8 TROUBLESHOOTING 8 12 MEMO ...
Page 219: ...9 OUTLINE DRAWINGS 9 6 MEMO ...
Page 229: ...10 CHARACTERISTICS 10 10 MEMO ...
Page 295: ...13 USING STO FUNCTION 13 14 MEMO ...
Page 327: ...14 USING A LINEAR SERVO MOTOR 14 32 MEMO ...
Page 371: ...16 FULLY CLOSED LOOP SYSTEM 16 24 MEMO ...
Page 521: ...APPENDIX App 38 ...
Page 537: ...MEMO ...
Page 541: ......