110
Learning Basic Features
4.9 Reset and Restart
Reset and restart operations can be setup for inverter operation following a fault trip, based
on the terminal block operation command (if it is configured). When a fault trip occurs, the
inverter cuts off the output and the motor will free-run. Another fault trip may be triggered if
the inverter begins its operation while motor load is in a free-run state. In PRT-08, bit 1 sets
the option for all the fault trips, other than low voltage trips, and bit 2 sets the option for low
voltage trips. PRT-10 sets the delay time for restart (the time for the inverter to wait before it
restarts).
The number of auto-restarts (PRT-09) refers to the number of times the inverter will try
restarting its operation. If fault trips occur again after restart, the retry number counts down
each time the inverter restarts until the number becomes ‘0.’ Once the inverter restarts
successfully after the initial fault trip, the inverter does not restart until the next fault trip
occurs. The number of auto-restarts set at PRT-09 that decreased after a restart reverts to
the original setting value if successful operation continues for certain period of time.
Group Code Name
LCD
Display
Parameter Setting
Setting
Range
Unit
DRV 06
Command source
Cmd
Source
1 Fx/Rx-1
0
–5
-
PRT
08
Reset restart setup
RST
Restart
00
00
–11
Bit
09
No. of auto restart
Retry
Number
6
0
–10
-
10
Auto restart delay
time
Retry
Delay
5.0
0.1
–600.0
sec
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...