189
Learning Advanced Features
5.11 Lubrication Operation
During a lubrication operation, the inverter outputs the lubrication signal through one of the
output relays when the inverter receives a run command. The inverter does not start
operating until the time set at AP2-46 (Lub Op Time) has elapsed and the Lubrication signal
is turned off.
Group
Code
Name
LCD Display Parameter Setting Setting Range Unit
AP2
46
Lubrication
operation time
Lub Op
Time
0.1
–600.0
(sec)
OUT
31-35
Multi-function
relay 1
–5
Relay 1
–5
33 (Damper
Control)
-
-
Lubrication Operation Setting Details
Code
Description
AP2-46 Lub Op
Time
Outputs the lubrication signal for a set time when the inverter run
command is turned on. The inverter starts operating when the set time
has elapsed.
OUT-31
–35
Relay 1
–5
Sets one of the output relays (OUT-31
–35) to ‘30 (Lubrication)’ to enable
the Lubrication function.
Note
•
The lubrication function can be used to delay inverter operations, depending on the
working environment, since the inverter waits for the time set at AP2-46 (Lub Op Time)
each time a run command is received.
•
Lubrication operation is one of the essential system features that are available in both
HAND and AUTO modes.
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...