5.7 Slip Compensation Operation
Slip refers to the variation between the setting frequency (synchronous speed) and motor
rotation speed. As the load increases there can be variations between the setting frequency
and motor rotation speed. Slip compensation is used for loads that require compensation of
these speed variations.
Group Code
Name
LCD Display Parameter Setting
Setting Range
Unit
DRV
09
Control Mode
Control
Mode
1
Slip
Compen
-
-
14
Motor Capacity
Motor
Capacity
2
5.5 kW 0
–20
-
BAS
11
Number of
motor poles
Pole
Number
4
2
–48
-
12
Rated slip
speed
Rated Slip
40 (5.5 kW based)
0
–3000
Rp
m
13
Rated motor
current
Rated Curr
3.6 (5.5 kW based) 1.0
–1000.0
A
14
Motor no-load
current
Noload Curr 1.6 (5.5 kW based) 0.5
–1000.0
A
16
Motor
efficiency
Efficiency
72 (5.5 kW based)
70
–100
%
Slip Compensation Operation Setting Details
Code
Description
DRV-09 Control Mode
Set DRV-
09 to ‘2 (Slip Compen)’ to carry out the slip compensation
operation.
DRV-14 Motor Capacity Set the capacity of the motor connected to the inverter.
BAS-11 Pole Number
Enter the number of poles from the motor rating plate.
BAS-12 Rated Slip
Enter the number of rated rotations from the motor rating plate.
𝑓
𝑠
= 𝑓
𝑟
−
𝑅𝑝𝑚 × 𝑃
120
𝑓
𝑠
= Rated slip frequency
𝑓
𝑟
= Rated frequency
𝑅𝑝𝑚
= Number of the rated motor rotations
𝑃
=
Number of motor poles
BAS-13 Rated Curr
Enter the rated current from the motor rating plate.
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...