Learning Basic Features
4.18.3 Frequency Jump
Use frequency jump to avoid mechanical resonance frequencies. The inverter will avoid
identified ranges during acceleration and deceleration. Operation frequencies cannot be set
within the pre-set frequency jump band.
When a frequency setting is increased, while the frequency parameter setting value
(voltage, current, RS-485 communication, keypad setting, etc.) is within a jump frequency
band the frequency will be maintained at the lower limit value of the frequency band. Then,
the frequency will increase when the frequency parameter setting exceeds the range of
frequencies used by the frequency jump band.
Group Code Name
LCD Display
Parameter
Setting
Setting Range
Unit
ADV
27
Frequency jump
Jump Freq
0 0
–1
0
–1
-
28
Jump frequency
lower limit1
Jump Lo 1
10.00
0.00
–Jump frequency
upper limit 1
Hz
29
Jump frequency
upper limit1
Jump Hi 1
15.00
Jump frequency lower
limit 1
–Maximum
frequency
Hz
30
Jump frequency
lower limit 2
Jump Lo 2
20.00
0.00
–Jump frequency
upper limit 2
Hz
31
Jump frequency
upper limit 2
Jump Hi 2
25.00
Jump frequency lower
limit 2
–Maximum
frequency
Hz
32
Jump frequency
lower limit 3
Jump Lo 3
30.00
0.00
–Jump frequency
upper limit 3
Hz
33
Jump frequency
upper limit 3
Jump Hi 3
35.00
Jump frequency lower
limit 3
–Maximum
frequency
Hz
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...