289
Learning Advanced Features
Multi-function Output On/Off Control Setting Details
Code
Description
ADV-66 OnOff Ctrl Src
Select analog input On/Off control.
ADV-67 On Ctrl Level ,
ADV-68 Off Ctrl Level
Set On/Off level at the output terminal.
5.46 Press Regeneration Prevention
Press regeneration prevention is used during press operations to prevent braking during the
regeneration
process. If motor regeneration occurs during a press operation, motor operation
speed automatically goes up to avoid the regeneration zone
.
Group Code Name
LCD Display Parameter Setting Setting Range Unit
ADV
74
Select press
regeneration
prevention for press
RegenAvd
Sel
0
No
0
–1
-
75
Press regeneration
prevention operation
voltage level
RegenAvd
Level
350 V
200 V class:
300
–400 V
V
700 V
400 V class:
600
–800 V
76
Press regeneration
prevention
compensation
frequency limit
CompFreq
Limit
1.00 (Hz)
0.00
–10.00
Hz
Hz
77
Press regeneration
prevention P-Gain
RegenAvd
Pgain
50.0 (%)
0 .0
–100.0%
%
78
Press regeneration
prevention I gain
RegenAvd
Igain
500 (ms)
20
–30000 ms ms
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...