111
Learning Basic Features
Note
•
To prevent a repeat fault trip from occurring, set CON-71 (speed search options) bit 2 the
same as bit 1. The inverter will perform a speed search at the beginning of the operation.
•
If the speed search is not enabled, the inverter will start its operation in a normal V/F
pattern and accelerate the motor. If the inverter has been turned on without ‘reset and
restart’ enabled, the terminal block command must be first turned off, and then turned on
again to begin the inverter’s operation.
4.10 Setting Acceleration and Deceleration Times
4.10.1 Acc/Dec Time Based on Maximum Frequency
Acc/Dec time values can be set based on maximum frequency, not on inverter operation
frequency. To set Acc/Dec time values based on maximum frequency, set BAS- 08
(Acc/Dec reference) in the Basic group to ‘0 (Max Freq)’.
Acceleration time set at DRV-03 (Acceleration time) refers to the time required for the
inverter to reach the maximum frequency from a stopped (0 Hz) state. Likewise, the value
set at the DRV-04 (Deceleration time) refers to the time required to return to a stopped state
(0 Hz) from the maximum frequency.
Group Code
Name
LCD Display Parameter Setting
Setting Range
Unit
DRV
03
Acceleration
time
Acc Time
20.0
0.75~90KW
0.0
–600.0
sec
60.0
110~250KW
100.0
315~500KW
04
Deceleration
time
Dec Time
30.0
0.75~90KW
0.0
–600.0
Sec
90.0
110~250KW
150.0
315~500KW
20
Maximum
frequency
Max Freq
60.00
40.00
–400.00 Hz
BAS
08
Acc/Dec
reference
Ramp T
Mode
0
Max Freq
0
–1
-
Use caution when operating the inverter with Power-on Run enabled as the motor will
begin rotating when the inverter starts up.
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...