182
Learning Advanced Features
EPID Basic Operation Setting Details
Code
Description
EPI-01 EPID1 Mode
Sets the EPID1 modes.
Setting
Function
0
None
EPID1 is not used.
1
Always On
EPID1 operates at all times.
2
During Run
Operates only when the inverter is running.
3
DI
Dependent
Operates when terminal input (EPID1 Run)
is on.
EPI-02 PID Output
Displays the existing output value for the EPID controller. The unit,
gain, and scale that were set in the EPID group are applied on the
display.
EPI-03 EPID Ref Value
Displays the existing reference value set for the EPID controller.
The unit, gain, and scale that were set in the EPID group are
applied on the display.
EPI-04 EPID1 Fdb
Value
Displays the existing feedback value set for the EPID controller.
The unit, gain, and scale that were set in the EPID group are
applied on the display.
EPI-05 EPID1 Err
Value
Displays the difference between the existing reference and the
feedback (error value). The unit, gain, and scale that were set in the
PID group are applied on the display.
EPI1-06 EPID1 Ref Src
Selects the reference input for the EPID control. If the V1 terminal is
set to an EPID1 feedback source (EPID1 F/B Source), V1 cannot
be set as the EPID1 reference source (EPID1 Ref Source). To set
V1 as a reference source, change the feedback source.
Setting
Function
0
Keypad
Keypad
1
V1
-10-10 V input voltage terminal
3
V2
I2 analog input terminal [When analog
voltage/current input terminal selection switch
(SW2) at the terminal block is set to I
(current), input 0-20 mA current. If it is set to V
(voltage), input 0
–10 V]
4
I2
5
Int. 485
RS-485 input terminal
7
FieldBus
Communication command via a
communication option card
8
Pulse
TI Pulse input terminal (0-32 kHz Pulse input)
EPI-07 EPID1 Ref Set
Set the EPI control reference type (EPI-
06) to ‘0 (Keypad)’ to enter
the reference value.
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...