Perform Basic Operations
62
User & Macro mode and Trip mode are not displayed when all the inverter settings are set
to the factory default (User & Macro mode must be configured before it is displayed on the
keypad, and Trip mode is displayed only when the inverter is at fault, or has previous trip
fault history).
3.2.2 Operation Modes
The inverter is operable only when it is in HAND or AUTO mode. HAND mode is for local
control using the keypad, while AUTO mode is for remote control via communication. On
the other hand, the inverter stops operating when it is in OFF mode. Select one of the
modes (HAND / AUTO / OFF) to operate the inverter or stop the operation.
Follow the examples below to learn how to switch between operation modes.
Operating the Inverter in HAND mode
1
Turn on the inverter. The inverter enters OFF mode and the OFF LED turns on.
2
Move to Parameter mode and set DRV-07 (frequency reference)
to ‘0 (keypad)’.
3
Press the [HAND] key to enter HAND mode (local control mode). HAND mode LED
turns on (the OFF LED turns off) and the inverter begins to operate.
4
Press the [OFF] key to stop the inverter operation. The inverter stops operating and the
OFF LED turns on.
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...