Learning Protection Features
310
Code
Description
PRT-34
Thermal-T Sel
Sets the inverter operation state when motor is overheated.
Setting
Function
0
None
Do not operate when motor overheating is detected.
1
Free-Run
When the motor is overheated, the inverter output is
blocked and the motor will free-run by inertia.
3
Dec
When the motor is over heated, the motor
decelerates and stops.
PRT-35
Thermal In Src
Selects the type of the terminal when the motor overheat protect sensor
is connected to the volt (V1) or current (I2) input terminal of the terminal
block in the inverter.
Setting
Function
0
Thermal In
Configure the motor overheat protect sensor
connection to terminal block V1.
1
V2
Configure the motor overheat protect sensor
connection to terminal block I2.
PRT-36
Thermal-T Lev
Configure the fault level of the motor overheat detect sensor.
PRT-37
Thermal-T Area
Setting
Function
0
Low
Operates when the motor overheat sensor input is
smaller than PRT-36.
1
High
Operates when the motor overheat sensor input is
bigger that PRT-36.
OUT-07 AO2 Mode,
OUT-08 AO2 Gain
Used when supplying the constant current to the temperature sensor
and receives input through the I2 or V1 terminal block by using the
analog output terminal.
Using the temperature sensor (PTC) by connecting it to the analog input terminal
When the AO2(analog current output) terminal is connected to the temperature sensor
installed on a motor, the inverter supplies constant current to the temperature sensor. Then,
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...