527
Troubleshooting
LCD Display
Description
Over Load
Displayed when a motor is overloaded. Set PRT-
17 to ‘1’ to enable. Set
OUT-31
–35 or OUT-36 to ‘5 (Over Load)’ to receive the overload warning
output signals.
Under Load
Displayed when the motor is underloaded. Set PRT-
25 is to ‘1’. Set the
digital output terminal or relay (OUT-31
–35 or OUT-36) to’ 7 (Under
Load)’ to receive the underload warning output signals.
INV Over Load
Displayed when the overload time equivalent to 60% of the inverter
overheat protection (inverter IOLT) level, is accumulated. Set the digital
output terminals or relay (OUT-31
–35 or OUT-36) to ‘6 (IOL)’ to receive
the inverter overload warning output signals.
Lost Command
Lost command warning alarm occurs even with PRT-
12 set to ‘0’. The
warning alarm occurs based on the condition set at PRT-13-15. Set the
digital output terminals or relay (OUT-31
–35 or OUT-36) to ‘13 (Lost
Command
)’ to receive the lost command warning output signals.
Fan Warning
Displayed when an error is detected from the cooling fan while PRT-79 is
set to’1’. Set the digital output terminals or relay (OUT-31–35 or OUT-36)
to ‘8 (Fan Warning)’ to receive the fan warning output signals.
DB Warn %ED
Displayed when the DB resistor usage rate exceeds the set value. Set
the detection level at PRT-66.
Fire Mode
When there is a fire, Fire Mode forces the inverter to ignore certain fault
trips and continue to operate. Set the digital output terminals or relay
(OUT-31
–35 or OUT-36) to ‘27 (Fire Mode)’ to receive the fire mode
warning output signals.
Pipe Broken
Displayed when a pipe is broken during pump operation. Set the digital
output terminals or relay (OUT-31
–35 or OUT-36) to ‘28 (Pipe Broken)’ to
receive the pipe break warning output signals.
Lost Keypad
Displayed when a communication error occurs between the keypad and
the inverter, when PRT-11 (Lost KPD Mode) is set to any other value
than ‘0’, and a run command is given from the keypad. Set the digital
output terminals or relay (OUT-31
–35 or OUT-36) to ‘24 (Lost KPD)’ to
receive the lost keypad warning output signals.
Level Detect
Displayed during a level detect state. Set PRT-
70 to ‘1 (warning)’ to
enable.
CAP. Warning
Displayed when capacitor life expectancy level goes below the level set
by the user. Set the digital output terminals or relay (OUT-31
–35 or OUT-
36) to ‘34 (CAPWarning)’ to receive the capacitor life warning output
signals.
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...