![LS ELECTRIC LSLV-H100 Series User Manual Download Page 151](http://html1.mh-extra.com/html/ls-electric/lslv-h100-series/lslv-h100-series_user-manual_1943798151.webp)
138
Learning Basic Features
•
When setting the multi-function terminal to the 2nd command source (2nd Source) and
input (On) the signal, operation state is changed because the frequency setting and the
Operation command will be changed to the 2nd command. Before shifting input to the
multi-function terminal, ensure that the 2nd command is correctly set. Note that if the
deceleration time is too short or inertia of the load is too high, an overvoltage fault trip may
occur.
•
Depending on the parameter settings, the inverter may stop operating when you switch the
command modes.
4.20 Multi-function Input Terminal Control
Filter time constants and the type of multi-function input terminals can be configured to
improve the response of input terminals.
Group Code
Name
LCD Display
Parameter Setting Setting Range Unit
IN
85
Multi-function input
terminal On filter
DI On Delay
10
0
–10000
mse
c
86
Multi-function input
terminal Off filter
DI Off Delay
3
0
–10000
mse
c
87
Multi-function input
terminal selection
DI NC/NO Sel 000 0000*
-
-
90
Multi-function input
terminal status
DI Status
000 0000*
-
-
* From the last bit to the first, the bits are for multi-purpose input 1
–7 (the last bit is for input
1, and the first bit for input 7).
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...