Applying Drives to Single-
phase Input Application
582
Figure-2 Typical Single-Phase Configuration
12.2 Power(HP), Input Current and Output Current
When using a three-phase VFD with single-
phase input, derating the drive’s output current
and horsepower will be necessary because of the increase in DC bus ripple voltage and
current.
In addition, the input current through the remaining two phases on the diode bridge
converter will approximately double, creating another derating consideration for the VFD.
Input current harmonic distortion will increase beyond that with a three-phase supply
making the overall input power factor low. Input current distortion over 100% is likely under
single-phase conditions without a reactor.
Therefore, the reactor is always required. When using a motor that is selected by the three-
phase drive rating criteria when using single-phase input, it may result in poor performance,
premature drive failure. The selected drive of single-phase current ratings must meet or
exceed the motor current rating.
In case of single-phase input, the rating of the inverter is smaller than that of the motor.
Please check the rating table of 11.1.
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...