Learning Protection Features
328
Group Code Name
LCD Display Parameter Setting
Setting range
Unit
PRT
81
Low voltage trip
decision delay time
LVT Delay
0.0
0
–60.0
sec
OUT
31
–
35
Multi-function relay
1
–5
Relay 1
–5
11
Low
Voltage
-
36
Multi-function
output 1
Q1 Define
Low Voltage Fault Trip Setting Details
Code
Description
PRT-81
LVT Delay
If the code value is set to ‘11 (Low Voltage)’, the inverter stops the output first
when a low voltage trip condition occurs, then a fault trip occurs after the low
voltage trip decision time elapses. The warning signal for a low voltage fault trip
can be provided using the multi-function output or a relay. However, the low
voltage trip delay time (LVT Delay time) does not apply to warning signals.
6.3.3 Selecting Low Voltage 2 Fault During Operation
Group Code Name
LCD Display
Setting
Setting range
Unit
PRT
82
Low voltage trip
decision during
operation
LV2 Trip Sel
0
No
0
–1
If input power is disconnected during inverter operation and internal DC voltage decreases
lower than a certain voltage, the inverter disconnects the output and dis
plays low voltage ‘2
(Low Voltage 2)'.
Even if the voltage increases and goes back to the normal state, unlike a low voltage fault, it
remains in a fault state until the user unlocks the fault state.
6.3.4 Output Block via the Multi-function Terminal
When the multi-function input terminal is set as the output block signal terminal and the
signal is input to the terminal, then the operation stops.
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...