209
Learning Advanced Features
The initial heating operation starts to run after an inverter operation stops, when the initial
heating function’s terminal input is on after the inverter operation command is off.
The diagram above shows the operation waveform related to AP2-50 DC Inj Delay T. The
Pre Heat function performs when the inverter stop mode is set to Free Run and the Pre
Heat signal is supplied. Then, if the inverter operation command is on, the inverter
maintains acceleration and a fixed frequency. If the inverter operation command is off, the
motor is in Free Run and the Pre Heat operations starts after the time amount set in AP2-
50.
•
If the value for AP2-48 Pre Heat Curr is above the rated motor current value, it is limited by
the rated motor current value.
•
If the value for AP2-48 Pre Heat Curr is too high or the DC current output time is too long
,
the motor may overheat or be damaged and the Inver IOLT may also malfunction. Reduce
the DC output current amount and DC output time to prevent from such damages.
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...