RS-485 Communication Features
376
Note
•
When setting parameters in the inverter memory control area, the values are reflected to
the inverter operation and saved. Parameters set in other areas via communication are
reflected to the inverter operation, but are not saved. All set values are cleared following
an inverter power cycle and revert back to its previous values. When setting parameters
via communication, ensure that a parameter save is completed prior to shutting the
inverter down.
•
Set parameters very carefully. After setting a parameter to ‘0’ via communication, set it to
another
value. If a parameter has been set to a value other than ‘0’ and a non-zero value
is entered again, an error message is returned. The previously-set value can be identified
by reading the parameter when operating the inverter via communication.
•
The addresses 0h03E7 and 0h03E8 are parameters for entering the password. When the
password is entered, the condition will change from Lock to Unlock, and vice versa. When
the same parameter value is entered continuously, the parameter is executed just once.
Therefore, if the same value is entered again, change it to another value first and then re-
enter the previous value. For example, if you want to enter 244 twice, enter it in the
following order: 244
0
244.
•
If the communication parameter settings are initialized by setting the address 0h03E2 to
[1: All Grp] or [8: COM Grp], or if any Macro function item is modified by setting the
address 0h03E4, all the communication parameter settings are reverted to the factory
default. If this happens, the inverter may not be able to properly receive responses from
the upper-level devices due to the changes in the settings.
•
If there is an undefined address in the addresses for reading multiple consecutive data
defined in the common area, the undefined address returns0xFFFF while all the others
return normal response. If all the consecutive addresses are undefined, one return code
is received from the first undefined address only.
•
If there is an undefined address in the addresses for writing into multiple consecutive data
defined in the common area, or if the value that is being written is not a valid one, no error
response about the wring operation is returned. If all the consecutive addresses are
undefined, or if all the date is invalid, one return code is received from the first undefined
address only.
It may take longer to set the parameter values in the inverter memory control area because all
data is saved to the inverter. Be careful as communication may be lost during parameter setup if
parameter setup is continues for an extended period of time.
0h03EC
Initialize cooling fan
accumulated operation
time
-
-
O
0: No, 1: Yes
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...