88
Learning Basic Features
You can set and modify a frequency reference by setting voltage inputs when using the V1
terminal. Use voltage inputs ranging from 0
–10 V (unipolar) for forward only operation. Use
voltage inputs ranging from -10 to +10 V (bipolar) for both directions, where negative
voltage inputs are used in reverse operations.
4.2.3.1 Setting a Frequency Reference for 0
–10 V Input
Set IN-
06 (V1 Polarity) to ‘0 (unipolar)’. Use a voltage output from an external source or use
the voltage output from the VR terminal to provide inputs to V1. Refer to the diagrams
below for the wiring required for each application.
[External source application]
[Internal source (VR) application]
Group Code Name
LCD Display
Parameter
Setting
Setting Range
Unit
DRV
07
Frequency
reference source
Freq Ref
Src
2
V1
0
–11
-
IN
01
Frequency at
maximum analog
input
Freq at
100%
Maximum
frequency
0.00
–
Max.
Frequency
Hz
05
V1 input monitor
V1
Monitor[V]
0.00
0.00
–12.00
V
06
V1 polarity options
V1 Polarity
0
Unipolar
0
–1
-
07
V1 input filter time
constant
V1 Filter
10
0
–10000
msec
08
V1 minimum input
voltage
V1 volt x1
0.00
0.00
–10.00
V
09
V1 output at
minimum voltage
(%)
V1 Perc y1
0.00
0.00
–100.00
%
10
V1 maximum input
voltage
V1 Volt x2
10.00
0 .00
– 12.00
V
11
V1 output at
maximum voltage
(%)
V1 Perc y2
100.00
0
–100
%
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...