239
Learning Advanced Features
Code
Description
LCD Display
Reset Restart function
Setting
Function
Bit1
Bit 0
For fault trips other than LV
For LV fault trips
For fault trips other than LV
: If the Bit 0 is turned on, the inverter
restarts after a trip occurs and triggers a reset.
For LV fault trips
: If the Bit 1 is turned on, the inverter restarts after a
trip occurs and triggers a reset.
PRT-09
Retry Number,
PRT-10
Retry Delay
The number of available auto restarts can be set at PRT-09. If a fault
trip occurs during an operation, the inverter restarts after the time set at
PRT-10 (Retry Delay). At each restart, the inverter counts the number of
tries and subtracts it from the number set at PRT-09 until the retry
number count reaches 0. After an auto restart, if a fault trip does not
occur within 60 sec, it will increase the restart count number. The
maximum count number is limited by the number set at PRT-09.
If the inverter stops due to over current or hardware diagnosis, an auto
restart is not activated. At auto restart, the acceleration options are
identical to those of speed search operation. Codes CON-72
–75 can be
set based on the load. Information about the speed search function can
be found at 5.27 Speed Search Operation on page
[Example of auto restart with a setting of 2]
•
If the auto restart number is set, be careful when the inverter resets from a fault trip. The
motor may automatically start to rotate.
•
In HAND mode, auto restart resets the trip condition but it does not restart the inverter
operation.
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...