206
Learning Advanced Features
5.19 Pipe Break Detection
This function detects Pipe Breaks while the PID operation is on. The fault trip or a warning
signal will occur if the feedback does not reach the level set by users during the operation
with the maximum output (PID maximum output or the maximum speed set).
Group Code
Name
LCD Display Parameter Setting Setting Range
Unit
PRT
60
Pipe Break
Detection setting
PipeBroken
Sel
0
0 None
1 Warning
2 Free-Run
3 Dec
61
Pipe Break
Detection variation
PipeBroken
Dev
97.5
0
–100
%
62
Pipe Break
Detection time
PipeBroken
DT
10.0
0
–6000.0
Sec
OUT
31
–36 Relay output 1–5
Relay1
–5
28
Pipe Broken
-
Pipe Break Detection Details
Code
Description
PRT-60
PipeBroken Sel
Select the operation while detecting Pipe Breaks
Setting
Function
0
None
No operation
1
Warning
The inverter displays a warning message.
2
Free-Run
The inverter free-runs, then stops.
3
Dec
The inverter decelerates, then stops.
PRT-61
PipeBroken Dev
Sets the Pipe Break Detection level. Set the detect level by multiplying the
set value for PRT-61 by PID Reference.
PRT-62
PipeBroken DT
Sets the detect delay time. Pipe Break operates if the Pipe Break situation
is maintained for a set amount of time.
OUT31
–36
Define
If Pipe Break (28) is set, when a Pipe Break occurs, the inverter sends out
output with Relay.
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...