143
Learning Advanced Features
5.1 Operating with Auxiliary References
Frequency references can be configured with various calculated conditions that use the
main and auxiliary frequency references simultaneously. The main frequency reference is
used as the operating frequency, while auxiliary references are used to modify and fine-tune
the main reference.
Group Code LCD Display
LCD Display Parameter Setting
Setting Range Unit
DRV
06
Frequency
reference source
Freq Ref
Src
0
Keypad-1 0
–11
-
BAS
01
Auxiliary frequency
reference source
Aux Ref Src 1
V1
0
–13
-
02
Auxiliary frequency
reference
calculation type
Aux Calc
Type
0
M+(G*A)
0
–7
-
03
Auxiliary frequency
reference gain
Aux Ref
Gain
100.0
100.0
-200.0
–200.0 %
IN
65
–
71
Px terminal
configuration
Px Define
36
dis Aux
Ref
0
–55
-
The table above lists the available calculated conditions for the main and auxiliary
frequency references. Refer to the table to see how the calculations apply to an example
where the DRV-
06 Frq Src code has been set to ‘0 (Keypad-1)’, and the inverter is
operating at a main reference frequency of 30.00 Hz. Signals at -10 to +10 V are received
at terminal V1, with the reference gain set at 5%. In this example, the resulting frequency
reference is fine-tuned within the range of 27.00
–33.00 Hz [Codes IN-01–16 must be set to
the default values, and IN-
06 (V1 Polarity), set to ‘1 (Bipolar)’].
Auxiliary Reference Setting Details
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...