Learning Advanced Features
MMC Setting Details
Code
Description
AP1-40 MMC Sel
Selects the MMC operation settings.
-None : Deactivates MMC function
-Single Ctrl : Activates general MMC function
-Multi Follower : Activates Master Follower as Multi Follower
mode
-Multi Master: Activates Master Follower as Multi Master mode
-Serve Drv: Sets Serve Drv used at Master Follower.
AP1-42 Num of Aux
Decides the number of auxiliary motors to use.
AP1-43 Starting Aux
Sets the start auxiliary motor.
AP1-44 Aux Motor Run
Indicates the number of the operating auxiliary motors.
AP1-45
–46 Aux Priority1–2
Indicates the operating priority of auxiliary motors.
According to setting by users, it can be influenced by Interlock,
AutoChange and operating time
Each four-digit numbers for the parameter mean the auxiliary
motor numbers and indicate the priority of auxiliary motors. In
other words, the most right number of [AP1-45 Aux Priority1]
indicates the priority of Auxiliary motor 1 and the second
number from the right of [AP1-45 Aux Priority1] indicates the
priority of Auxiliary motor 2.
[AP1-45 Aux Priority1]
x
x
x
x
The Priority of
the Aux motor1
The Priority of
the Aux motor4
[AP1-46 Aux Priority2]
x
x
x
x
The Priority of
the Aux motor5
The Priority of
the Aux motor8
AP1-48 Aux All Stop
When [AP1-
48 Aux All Stop] is set to “No” during input to stop
operating, auxiliary motors are turned off at the same time.
When [AP1-48 Aux All
Stop] is set to “YES”, auxiliary motors are
turned off gradually based on time of [AP1-54 Aux Stop DT].
AP1-49 FIFO/FILO
Sets the operating priority of MMC.
FIFO : Same as On/Off order of auxiliary motors.
FILO: Opposite to On/Off order auxiliary motors.
Op Time Order : setting automatically according to operating
time of auxiliary motors.
AP1-50 Aux Start Diff
AP1-59 Aux Stop Diff
One of the conditions to turn on and off the next auxiliary motors.
Parameters to set the difference when the difference between
the reference and feedback is more than regular value
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...