Learning
Protection Features
311
connecting the motor signal wire to one of the
inverter’s analog input terminals allows the
inverter to detect the changes in the PTC resistance and translates it into voltage. If the I2
terminal is used to receive the signal, set the selection switch on the I/O board to V2. If the
V1 terminal is used, set the switch to T1.
The sensor does not operate if SW3 is set to’ V1’.
To receive PTC signal at V1 input terminal, set PRT-
35 (Thermal InSrc) to ‘0 (Thermal In)’
and set the Analog1 input selection switch (SW3) to T1.
To receive PTC signal at I2 input terminal, set PRT-
35 (Thermal InSrc) to ‘1 (V2)’ and set
SW 4 (Analog2 input selection switch) to V2. The sensor does not operate if SW4 is set to
‘I2’.When the inverter detects a motor overheat, motor overheat trip occurs with internal
delay time. The trip delay time is not reset instantly when the trip condition is released, but it
only decreases as time passes.
6.1.3 Overload Early Warning and Trip
Group Code Name
LCD Display
Parameter Setting Setting range
Unit
PRT
17
Overload warning
selection
OL Warn
Select
1
Yes
0
–1
-
18
Overload warning
level
OL Warn Level 110
30
–120
%
19
Overload warning
time
OL Warn Time
10.0
0
–30
sec
20
Motion at overload
trip
OL Trip Select
1
Free-Run
-
-
21
Overload trip level
OL Trip Level
120
30
–150
%
22
Overload trip time
OL Trip Time
60.0
0
–60.0
sec
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...