187
Learning Advanced Features
5.10 Damper Operation
A damper is a device that controls the flow in a ventilation system. If a fan and a damper are
used together in a system, the inverter may be configured to operate according to the
damper’s operation status. During a damper operation, one of the relay outputs
OUT-31
–35
(Relay 1
–5) may be set to ‘33 (Damper Control)’ to output a signal based on the damper’s
operation status. O
ne of the multi-function terminal inputs (IN-65
–71) may also be set to ‘45
(Damper Open)’ to receive the damper status input. The inverter starts operating when both
the run command and the damper open signal are turned on (relay output setting at
OUT-
31
–35 is not necessary)
.
When the time difference between the inverter run command and the damper open signal
exceeds the delay time set at AP2-45 (Damper DT), damper error (Damper Err) occurs. If
the damper open relay output and damper control input are set at the same time, and if the
damper open signal is not received until the time set at AP2-45 (Damper DT) is elapsed
(when the inverter is not operating), damper error (Damper Err) occurs.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range Unit
AP2
45
Damper check
time
Damper DT
-
0.1
–600.0
sec
IN
65-71
P1
–7 Px
terminal
configuration
P1
–P7
Define
45
(Damper open)
-
-
OUT
31-35
Multi-function
relay 1
–5
Relay 1
–5
33
(Damper Control)
-
-
Damper Operation Setting Details
Code
Description
AP2-45 Damper DT
Sets the damper open delay time.
Detects the inverter run command or the damper open signal
(whichever is received first) and outputs a damper error (Damper Err) if
the other signal is not received until the time set at AP2-45 elapses.
IN-65
–71 P1–7
define
Sets one of the multi-
functional terminals to ’45 (Damper Open)’ to
enable damper operation.
OUT-31
–35 Relay
1
–5
Sets one of the relay outputs to ’33 (Damper Control)’ to provide a
relay output when the inverter run command is turned on.
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...