280
Learning Advanced Features
5.44.6 Regular Bypass
This function controls the motor speed based on the feedback amount instead of using the
PID. Auxiliary motors may be controlled with this feature based on the feedback amount.
Group Code Name
LCD Display
Parameter Setting
Setting Range Unit
AP1
41
Bypass selection
Regul Bypass 1
0 No
-
1 Yes
61
–
65
#1
–5 auxiliary
motor start
frequency
Start Freq
1
–5
Frequency value
within the range
Freq Low
Limit
–Freq
High limit
Hz
70
–
74
#1
–5 auxiliary
motor stop
frequency
Stop Freq
1
–5
Frequency value
within the range
Low Freq
–
High Freq
Hz
OUT
31
–
35
Multi-function
relay1
–5
Relay 1
–5
21
Multiple motor
control(MMC)
-
-
36
Multi-function 1
item
Q1 Define
40
KEB
Operation
-
-
Regular Bypass Detail Settings
Code
Description
AP1-41 Regular Bypass
Sets the regular bypass mode.
Mode Setting
0
No
1
Yes
AP1-61
–65 Start Freq 1–5 Sets the auxiliary motor start frequency.
AP1-70
–74 Stop Freq 1–5 Sets the auxiliary motor stop frequency.
OUT-31
–35 Relay 1–5
OUT-36 Q1 Define
Set OUT31
–35 to ’21 (MMC)’ to use the out terminal for auxiliary
motor operation. The number of configured output terminals
determines the total number of auxiliary motors to be used.
When an input set by the PID feedback of the analog input terminal (I or V1 or Pulse) is
100%, divide the area by the number of motors being used (including the main motor).
Each auxiliary motor turns on when feedback reaches the relevant level and turns off when
feedback goes below the relevant level. The primary motor increases its speed based on
the feedback and when it reaches the start frequency of the relevant auxiliary motor and
decelerates to the stop frequency.
The primary motor reaccelerates when the frequency increases, depending on the
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...