3. Make sure that the room temperature is within operating specifications.
4. If there are no other thermal issues, replace the I/O expansion adapter.
•
80070601-2c02ffff : Sensor Mezz Exp 2 temp has transitioned to non-recoverable.
The temperature of the I/O expansion adapter in I/O expansion connector 2 has exceeded its specified
threshold. The compute node has attempted a soft shutdown.
May also be shown as 800706012c02ffff or 0x800706012c02ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix:
PLAT
ID:
0530
User Response
Complete the following steps until the problem is solved:
1. Check the Chassis Management Module or Flex System Manager event log for any fan- or
cooling-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers
are in place and correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. If there are no other thermal issues, replace the I/O expansion adapter.
•
80070601-2c03ffff : Sensor PEN MExp 3 Temp has transitioned to non-recoverable.
The temperature of the PEN Mezzanine Expansion adapter in I/O expansion connector 3 has exceeded its
specified threshold. The compute node has attempted a soft shutdown.
May also be shown as 800706012c03ffff or 0x800706012c03ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
334
Flex System x220 Compute Node Installation and Service Guide
Summary of Contents for Flex System x220
Page 1: ...Flex System x220 Compute Node Installation and Service Guide Machine Types 7906 2585 ...
Page 50: ...42 Flex System x220 Compute Node Installation and Service Guide ...
Page 54: ...46 Flex System x220 Compute Node Installation and Service Guide ...
Page 68: ...60 Flex System x220 Compute Node Installation and Service Guide ...
Page 644: ...636 Flex System x220 Compute Node Installation and Service Guide ...
Page 698: ...690 Flex System x220 Compute Node Installation and Service Guide ...
Page 705: ...Taiwan BSMI RoHS declaration Appendix B Notices 697 ...
Page 706: ...698 Flex System x220 Compute Node Installation and Service Guide ...
Page 713: ......
Page 714: ...Part Number 00YJ297 Printed in China 1P P N 00YJ297 1P00YJ297 ...