Functional Desription
Operating and Unit Data
Adr.
min
max
default
Adr.
min
max
default
0201h
ru. 1
Set value display
0,125
rpm
-
4000
-4000
Display of Set value display. For check reasons the setpoint frequency is also displayed if the control release or the
direction of rotation are not switched. If no direction of rotation is preadjusted then the setpoint frequency for clockwise
rotation (forward) is indicated.
A counter-clockwise rotating field (reverse) is represented by a negative sign. Precondition is the in-phase connection
of the motor.
0202h
ru. 2
Ramp output display
0,125
rpm
-
4000
-4000
The displayed speed corresponds to the rotary field speed output at the ramp output. The representation is the same as
at ru.1.
clowckwise
rotation
(forward)
counter-clockwise
rotation
(reverse)
Adr.
min
max
default
6.1.5 Description of ru-Parameter
ru. 0 Inverter state
0200h
0
255
1
-
0
In parameter Ñinverter statusì the actual operating condition of the frequency inverter is displayed. In the case of an
error the current error message is displayed, even if the display has already been reset with ENTER (error-LED on the
operator is still blinking). Status messages and information about the cause and removal are to be found in Chapter 9
ÑError Diagnosisì.
Adr.
min
max
default
0203h
ru. 3
Actual frequency display
0,0125
Hz
-
400
-400
The indicated actual frequency corresponds to the rotary field frequency given out at the inverter output. The representation
is the same as at ru.1.