6.6 Motor Data and
Controller
Fig. 6.6.1
Example of a motor name plate
6.6.1 Motor Name Plate
The adjustment of the correct motor data is important for many inverter functions,
since calculations are derived from it, which the inverter requires to achieve the
best possible results in the control of Boost and slip compensation.
6.6.2 Motor Data DASM
Following parameters can be taken directly from the name plate of the three-phase
asynchronous motor (DASM) and entered:
- dr.0
DASM rated current
0,0...710,0 A (Star-/Delta-connection)
- dr.1
DASM rated speed
0...64000 rpm
- dr.2
DASM rated voltage
120...500 V (Star-/Delta-connection)
- dr.3
DASM rated power
0,35...400,00 kW
- dr.4
DASM power factor
cos(phi) 0,50...1,00
- dr.5
DASM rated frequency
0,0...400 Hz
Parameter dr.0 and dr.2 must always be adjusted in accordance with the used connection
(star or delta). For the above motor name plate it means that it is 230 V / 49,5A for
delta connection and 400 V / 28,5 A for star connection. It doesnít matter that for
example the rated output voltage of the inverter is larger (e.g. Ñ87Hz-chracteristicì).
dr.3
Motor data from name plate
(dr.0...dr.5)