Functional Desription
Setpoint- and Ramp Adjustment
Rotation adjustment via terminal
strip
oP.1 = Ñ2ì or Ñ3ì
F
R
F/R
Run/Stop
Input selection
Rotation direction F (Run/Stop) oP.60
Rotation direction R (forward/
reverse) oP.61
The rotation selection via terminal strip allows the adjustment of the direction of
rotation via switch or from a primary control.
With parameter oP.60 one input is determined for rotation direction forward (or run/
stop) and with oP.61 one input for rotation direction reverse (or forward/reverse).
The values in brackets are valid with oP.1 = Ñ4ì or Ñ5ì.
Bit -No. Decimal value
Input
Terminal
0
1
ST (Prog. input ÑControl release/Resetì)
X2A.16
1
2
RST (Prog. input ÑResetì)
X2A.17
2
4
F (Prog. input ÑForwardì)
X2A.14
3
8
R (Prog. input ÑReverseì)
X2A.15
4
16
I1 (Prog. input 1)
X2A.10
5
32
I2 (Prog. input 2)
X2A.11
6
64
I3 (Prog. input 3)
X2A.12
7
128
I4 (Prog. input 4)
X2A.13
8
256
IA (Internal input A)
none
9
512
IB (Internal input B)
none
10
1024
IC (Internal input C)
none
11
2048
ID (Internal input D)
none
In the case of rotation selection forward/reverse (oP.1= Ñ2ì or Ñ3ì) the inputs
determined with oP.60 and oP.61 work as follows:
Forward
Revers
Input
F
R
Function
0
0
LS
0
1
Reverse
1
0
Forward
1
1
Forward
In the case of rotation selection run/stop and forward/reverse (oP.1= Ñ4ì or Ñ5ì) the
inputs determined with oP.60 and oP.61 work as follows:
Revers
Forward
Input
F/R
Run/Stop Function
0
0
LS
0
1
Forward
1
0
LS
1
1
Reverse
oP.1 = Ñ4ì or Ñ5ì
X2A.14 X2A.15
X2A.14 X2A.15