2
1
KEB COMBIVERT F5
6
Name: Basis
04.05.04
©
KEB Antriebstechnik, 2002
All Rights reserved
Product Description
Summary
Chapter
Section
Page
Date
2.1.6
Unit Sizes 230V-Class
The following technical specifications refer to 2-/4-pole standard motors. In case of
different pole numbers the frequency inverter must be dimensioned for the rated
motor current. With regard to special or medium frequency motors, please contact
KEB.
Site altitude max. 2000 m. For altitudes of 1000 m or more above N.N. a power reduction
of 1 % per 100m must be taken into account.
2.1.5
Validity of
Specifications
05
07
09
10
12
13
A
A
B
B
D
B
D
D
E
1
1
3
1
1
3
1
3
1
3
1 3
1
3
3
3
[kVA]
0,9
1,6
2,8
4,0
6,6 9,5
[kW]
0,37
0,75
1,5
2,2
4,0 5,5
[A]
2,3
4
7
10
16,5 24
[A]
4,1
7,2
12,6
18
29,7 36
[A]
5,0
8,6
15,1
21,6
35,6 43
[A] 4,6 4,6 3,2 8,0 8,0 5,6 14 9,8 14 9,8 20 14 20 14 23
31
[A] ñ
3,7
ñ
ñ
6,4 ñ
ñ
ñ
ñ
ñ
[kW] ñ 0,85 ñ
ñ
1,5 ñ
ñ
ñ
ñ
ñ
[A] 10
16
10 20 16 20 16 20 16 25 20 25 20 25
35
[kHz] 4
16
8
16
16
8
16
8
8
[kHz] 4
16
8
16
16
16
16
16
[W] 30
55
65
90
130
105
170
210 290
[W] ñ
85
ñ
ñ 130 ñ
ñ
ñ
ñ
ñ
[A]
2,3
4
7
10
16,5 24
[A]
2,3
4
7
10
16,5 24
[A] ñ
2,3
ñ
4
7
8,5
10
10 16,8
[
∞
C]
90
[mm
≤
]
1,5
1,5 2,5 1,5 2,5 1,5 2,5 1,5 4 2,5 4 2,5
4
6
[Ohm] 100
56
100
56
47
33
27
16
[Ohm]
180
180
100
68
33
27
[A] 4,5
7,5
4,5
7,5
9,5
12
15
25
1
[Nm]
0,5
1,2
50
B
Inverter Size
Housing size
Phases
Output nominal power
Max. rated motor power
Output nominal current
Max. short time current
1)
OC-tripping current
Nominal input current
Nominal input current
2)
Real input rated power
2)
Max. permissible mains fuse (inert)
Rated switching frequency
Max. switching frequency
Power loss at nominal operating
Power loss at rated operation
2)
Stall current at 4kHz
3)
Stall current at 8kHz
3)
Stall current at 16kHz
3)
Max. heat sink temperature TOH
Motor line cross section
4)
Min. braking resistor
5)
Typ. braking resistor
5)
Max. braking current
Overload curve (page appendex)
Tightening torque for terminals
Mains voltage
Mains frequency
Output voltage
Output frequency
Max.shielded motor line length at 4 kHz
6)
Max.shielded motor line length at 8 kHz
6)
Max.shielded motor line length at 16 kHz
6)
Storage temperature
Operating temperature
Model / protective system
Relative humidity
EMC tested according to
Climatic category
[V]
180...260 ±0 (230 V Nominal voltage)
[Hz]
50 / 60 +/- 2
[V]
3 x 0...U Mains (3 x 0...255V
2)
)
[Hz]
see Control board
[m]
10
30
10
100
100
[m]
10
20
10
50
100
[m]
-
10
-
20
40
100
[
∞
C]
-25...70
∞
C
[
∞
C]
-10...45
∞
C
IP20
max. 95% without condensation
EN 61800-3
3K3 in accordance with EN 50178
1) With the regulated systems F5-M as well as F5-S 5% are to be subtracted as control reserve.
2) Fuses of type Ferraz Shawmut 6,6 UD Type 31
3) Max. current before the responding of the OL2-function (only F5-M; F5-S; F5-A)
4) Recommended minimum cross section for rated power and a cable length of upto 100m (copper)
5) This data is only valid for units with internal brake transistor (see "unit identification")
6) Rated voltage 400V; at mains voltage
≥
460V multiply the rated current with factor 0.86.
7) The temperature range is only valid for the control circuit. For the power circuit the temperature range is depending on the control cabinet
installation and the cooling system.
8) 31.F5 only watercooled.