
6
12
KEB COMBIVERT F5
10
Name: Basis
04.05.04
Chapter
Section
Page
Date
©
KEB Antriebstechnik, 2002
All rights reserved
Functional Description
Technology Control
Parameter
Addr.
min
max
default
[?]
Notes
cn 0
PID reference source
0700
X
X
–
0
4
1
0
–
–
cn 1
PID abs. reference
0701
X
X
–
-400,0
400,0
0,1
0,0
%
–
cn 2
PID act. value source
0702
X
X
–
0
7
1
0
–
–
cn 3
PID abs. act. value
0703
X
–
–
-400,0
400,0
0,1
0,0
%
–
cn 4
PID kp
0704
X
X
–
0,00
250,00
0,01
0,00
–
–
cn 5
PID ki
0705
X
X
–
0,000
30,000
0,001
0,000
–
–
cn 6
PID kd
0706
X
X
–
0,00
250,00
0,01
0,00
–
–
cn 7
PID pos. limit
0707
X
X
–
-400,0
400,0
0,1
400,0
%
–
cn 8
PID neg. limit
0708
X
X
–
-400,0
400,0
0,1
-400,0
%
–
cn 9
PID fading time
0709
X
X
–
-0,01
300,00
0,01
0,00
s
-0,01 freq. dependend
cn10 PID reset condition
070A
X
X
–
0
2
1
0
–
–
cn11 PID reset inp. sel.
070B
X
–
X
0
4095
1
0
–
–
cn12 I reset inp. sel.
070C X
–
X
0
4095
1
0
–
–
cn13 fade in reset inp. sel.
070D X
–
X
0
4095
1
0
–
–
cn14 PID out freq at 100%
070E
X
X
–
-400,0
400,0
0,0125
0
Hz
dependend on ud.2
ru13
Actual utilization
020D –
–
–
0
255
1
0
%
–
ru17
Active current
0211
–
–
–
-3276,7
3276,7
0,1
0
A
–
ru18
Actual DC voltage
0212
–
–
–
0
1000
1
0
V
–
ru28
AN1 post amplifier display
021C –
–
–
-400,0
400,0
0,1
0
%
–
ru30
AN2 post amplifier display
021E
–
–
–
-400,0
400,0
0,1
0
%
–
ru53
AUX display
0235
–
–
–
-400,0
400,0
0,1
0
%
–
6.12.5 Used Parameters