Goodrive300
inverters Communication protocol
244
space the program occupied is huge. So use it with caution according to the program
required space.
10.4 RTU command code and communication data illustration
10.4.1 command code:03H
03H(correspond to binary 0000 0011),read N words(Word)(the Max. continuous
reading is 16 words)
Command code 03H means that if the master read data form the inverter, the reading
number depends on the “data number” in the command code. The Max. continuous reading
number is 16 and the parameter address should be continuous. The byte length of every
data is 2 (one word). The following command format is illustrated by hex (a number with “H”
means hex) and one hex occupies one byte.
The command code is used to read the working stage of the inverter.
For example, read continuous 2 data content from0004H from the inverter with the address
of 01H (read the content of data address of 0004H and 0005H), the frame structure is as
below:
RTU master command message (from the master to the inverter)
START
T1-T2-T3-T4 (transmission time of 3.5 bytes)
ADDR
01H
CMD
03H
High bit of the start bit
00H
Low bit of the start bit
04H
High bit of data number
00H
Low bit of data number
02H
CRC low bit
85H
CRC high bit
CAH
END
T1-T2-T3-T4 (transmission time of 3.5 bytes)
T1-T2-T3-T4 between START and END is to provide at least the time of 3.5 bytes as the
leisure time and distinguish two messages for the avoidance of taking two messages as one
message.
ADDR
= 01H means the command message is sent to the inverter with the address of 01H
and ADDR occupies one byte
CMD
=03H means the command message is sent to read data form the inverter and CMD
occupies one byte
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...