Goodrive300
inverters Basic operation instruction
160
Function
code
Name
Detailed instruction of parameters
Default
value
5:Customized V/F(V/F separation)
P04.01
Torque boost of motor 1 0.0%:(automatic)0.1%~10.0%
0.0%
P04.02
Torque boost close of
motor 1
0.0%~50.0%(the rated frequency of
motor 1)
20.0%
P04.03
V/F
frequency 1 of motor 1
0.00Hz~P04.05
0.00Hz
P04.04
V/F
voltgage 1 of motor 1
0.0%~110.0%
00.0%
P04.05
V/F
frequency 2 of motor 1
P04.03~ P04.07
00.00Hz
P04.06
V/F
voltgage 2 of motor 1
0.0%~110.0%
00.0%
P04.07
V/F
frequency 3 of motor 1
P04.05~P02.02 or P04.05~P02.16
00.00Hz
P04.08
V/F
voltgage 3 of motor 1
0.0%~110.0%
00.0%
P04.09
V/F slip compensation
gain of motor 1
0.0~200.0%
0.0%
P04.10
Vibration control factor at
low frequency of motor 1
0~100
10
P04.11
Vibration control factor at
high frequency of motor 1
0~100
10
P04.12
Vibration control threshold
of motor 1
0.00Hz~P00.03 (the Max. frequency)
30.00 Hz
P04.13
Motor 2 V/F curve setting
0:Straight line V/F curve
;
applying to the
constant torque load
1:Multi-dots V/F curve
2:1.3
th
power low torque V/F curve
3:1.7
th
power low torque V/F curve
4:2.0
th
power low torque V/F curve
5:Customized V/F(V/F separation)
0
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...