![INVT GD300-004G-4 Operation Manual Download Page 300](http://html1.mh-extra.com/html/invt/gd300-004g-4/gd300-004g-4_operation-manual_2085739300.webp)
Goodrive300
inverters Appendix D
299
D.6 Reactors
High current in the input power circuit may cause damage to the rectifying components. It is
appropriate to use AC reactor in the input side for the avoidance of high-voltage input of the
power supply and improvement of the power factors.
If the distance between the inverter and the motor is longer than 50m, frequent overcurrent
protection may occur to the inverter because of high leakage current caused by parasitic
capacitance effects from the long cables to the ground. In order to avoid the damage of the
motor insulation, it is necessary to add reactor compensation.
The inverters of 380V (≥37Kw) and of 660V are equipped with internal DC reactors for the
improvement of power factors and the avoidance of damage from high input current to the
rectifying components because of the high-capacity transformer. The device can also cease
the damage to the rectifying components which are caused by supply net voltage transients
and harmonic waves of the loads.
D.6.1 AC 3PH 380V(-15%)~440V(+10%)
Model
Input reactor
DC reactor
Output reactor
GD300-1R5G-4
ACL2-1R5-4
/
OCL2-1R5-4
GD300-2R2G-4
ACL2-2R2-4
/
OCL2-2R2-4
GD300-004G-4
ACL2-004-4
/
OCL2-004-4
GD300-5R5G-4
ACL2-5R5-4
/
OCL2-5R5-4
GD300-7R5G-4
ACL2-7R5-4
/
OCL2-7R5-4
GD300-011G-4
ACL2-011-4
/
OCL2-011-4
GD300-015G-4
ACL2-015-4
/
OCL2-015-4
GD300-018G-4
ACL2-018-4
/
OCL2-018-4
GD300-022G-4
ACL2-022-4
/
OCL2-022-4
GD300-030G-4
ACL2-030-4
/
OCL2-030-4
GD300-037G-4
ACL2-037-4
DCL2-037-4
OCL2-037-4
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...