Goodrive300
inverters Appendix D
295
D.4.2.2 The inverters of AC 3PH 520V(-15%)~690V(+10%)
Recommended
cable size (mm
2
)
Connecting cable size (mm
2
)
Model
RST
UVW
PE
RST
UVW
P1,(+)
PB
(+),(-)
PE
Terminal
screw
Tightening
torque
(Nm)
GD300-022G-6
10
10
10~16
6~16
6~10
6~16
M8
9~11
GD300-030G-6
10
10
10~16
6~16
6~10
6~16
M8
9~11
GD300-037G-6
16
16
16~25 16~25
6~10
10~16
M8
9~11
GD300-045G-6
16
16
10~16 16~35 10~16
10~16
M8
9~11
GD300-055G-6
25
16
16~25 16~35 16~25
16~25
M10
18~23
GD300-075G-6
35
16
25~50 25~50 25~50
16~25
M10
18~23
GD300-090G-6
35
16
25~50 25~50 25~50
16~25
M10
18~23
GD300-110G-6
50
25
35~95 50~95 25~95
25
M10
18~23
GD300-132G-6
70
35
70~95 35~95 50~75
25~35
M10
18~23
GD300-160G-6
95
50
35~95
35~150 25~70 50~150
GD300-185G-6
95
50
35~95
35~150 25~70 50~150
GD300-200G-6
120
70
95~300 70~300 35~300 70~240
GD300-220G-6
185
95
95~300 70~300 35~300 95~240
GD300-250G-6
185
95
95~300 70~300 35~300 95~240
GD300-280G-6
240
120
95~300 95~300 70~300 120~240
GD300-315G-6
95*2P
95
95~150 70~150 70~150 35~95
GD300-350G-6
95*2P
95
95~150 70~150 70~150 35~95
GD300-400G-6
150*2P
150
95~150 70~150 70~150 50~150
GD300-500G-6
95*4P
95*2P
95~150 70~150 70~150 70~150
GD300-560G-6
95*4P
95*4P
95~150 70~150 70~150 70~150
GD300-630G-6
150*4P
150*2P
95~150 70~150 70~150 70~150
It is recommended to
use wrench or
sleeve because
screw is used as
terminal.
Note:
1. It is appropriate to use the recommended cable size under 40
℃
and rated current. The
wiring distance should be no more than 100m..
2. Terminals P1, (+), PB and (-) connects the DC reactor options and parts.
D.4.3 Routing the cables
Route the motor cable away from other cable routes. Motor cables of several drives can be
run in parallel installed next to each other. It is recommended that the motor cable, input
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...