![INVT GD300-004G-4 Operation Manual Download Page 72](http://html1.mh-extra.com/html/invt/gd300-004g-4/gd300-004g-4_operation-manual_2085739072.webp)
Goodrive300
inverters Function codes
71
Functi
on
code
Name
Detailed instruction of parameters
Default
value
Modif
y
P03.17
Keypad
setting for
upper
frequency
of reverse
rotation
50.00
Hz
○
P03.18
Upper
electromoti
on torque
source
0
○
P03.19
Upper
braking
torque
source
This function code is used to select the
electromotion and braking torque upper-limit
setting source selection.
0:Keypad setting upper-limit frequency(P03.20 sets
P03.18, P03.21 sets P03.19)
1: AI1
2: AI2
3: AI3
4: HDI
5:MODBUS communication
6:PROFIBUS communication
7:Ethernet communication
8: Reserved
Note: setting mode 1~9,100% corresponds to three
times of the motor current.
0
○
P03.20
Keypad
setting of
electromoti
on
torque
180.0%
○
P03.21
Keypad
setting of
braking
torque
The function code is used to set the limit of the
torque.
Setting range:0.0~300.0%(motor rated current)
180.0%
○
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...