Goodrive300
inverters Basic operation instruction
150
Function
code
Name
Detailed instruction of parameters
Default
value
P02.19
Rated current of
synchronous motor 1
0.8~6000.0A
Depend
on model
P05.01~P0
5.09
Multi-function digital input
terminals
(S1~S8,HDI) function
selection
36:Shift the command to keypad
37:Shift the command to terminals
38:Shift the command to communication
P07.01
Parameter copy
The function code determines the
manner of parameters copy.
0:No operation
1:Upload the local function parameter to
the keypad
2:Download the keypad function
parameter to local address(including the
motor parameters)
3:Download the keypad function
parameter to local address (excluding the
motor parameter of P02 and P12 group)
4:Download the keypad function
parameters to local address (only for the
motor parameter of P02 and P12 group)
0
P07.02
QUICK/JOG function
selection
0: No function
1: Jogging. Press QUICK/JOG to begin
the jogging running.
2: Shift the display state by the shifting
key. Press QUICK/JOGto shift the
displayed function code from right to left.
3: Shift between forward rotations and
reverse rotations. Press QUICK/JOG to
shift the direction of the frequency
commands. This function is only valid in
the keypad commands channels.
4: Clear UP/DOWN settings. Press
1
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...