Goodrive300
inverters Function codes
137
Functi
on
code
Name
Detailed instruction of parameters
Default
value
Modif
y
is shorter than the system processing time, then
the answer delay time is the system processing
time, if the answer delay is longer than the system
processing time, then after the system deal with the
data, waits until achieving the answer delay time to
send the data to the upper monitor.
P14.04
Fault time
of
communica
tion
overtime
0.0(invalid), 0.1~60.0s
When the function code is set as 0.0, the
communication overtime parameter is invalid.
When the function code is set as non-zero, if the
interval time between two communications
exceeds the communication overtime, the system
will report “485 communication faults” (CE).
Generally, set it as invalid; set the parameter in the
continuous communication to monitor the
communication state.
0.0s
○
P14.05
Transmissi
on fault
processing
0:Alarm and stop freely
1:No alarm and continue to run
2:No alarm and stop according to the stop mode
(only under the communication control)
3:No alarm and stop according to the stop mode
(under all control modes)
0
○
P14.06
Communic
ation
processing
0x00~0x11
LED ones:
0: Write with response: the inverter will respond to
all reading and writing commands of the upper
monitor.
1: Write without response: the inverter only
responds to the reading command other than the
writing command of the drive. The communication
efficiency can be increased by this method.
LED tens:(reserved)
0: Communication encrypting valid
0x00
○
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...