Goodrive300
inverters Function codes
47
restored.
4.
For a better parameter protection, the inverter provides password protection to the
parameters. After setting the password (set P07.00 to any non-zero number), the system will
come into the state of password verification firstly after the user press PRG/ESC to come
into the function code editing state. And then “0.0.0.0.0.” will be displayed. Unless the user
input right password, they cannot enter into the system. For the factory setting parameter
zone, it needs correct factory password (remind that the users can not modify the factory
parameters by themselves, otherwise, if the parameter setting is incorrect, damage to the
inverter may occur). If the password protection is unlocked, the user can modify the
password freely and the inverter will work as the last setting one. When P07.00 is set to 0,
the password can be canceled. If P07.00 is not 0 during powering on, then the parameter is
protected by the password. When modify the parameters by serial communication, the
function of the password follows the above rules, too.
Functi
on
code
Name
Detailed instruction of parameters
Default
value
Modif
y
P00 Group Basic function group
P00.00
Speed
control
mode
0: Sensorless vector control mode 0 (apply to AM
and SM)
No need to install encoders. It is suitable in cases
with low frequency, big torque and high speed
control accuracy for accurate speed and torque
control. Relative to mode 1, this mode is more
suitable for mediun and small power.
1: Sensorless vector control mode 1 (applying to
AM)
No need to install encoders. It is suitable in cases
with high speed control accuracy for accurate
speed and torque control at all power ratings.
2:V/F control
No need to install encoders. It can improve the
control accuracy with the advantages of stable
operation, valid low-frequency toruqe boost and
current vibration supression and the functions of
slip compensation and voltage adjustment.
1
◎
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...