Medium: double-shielded twisted pair cables,the shield can be removed according
to the environment (EMC).
●
Station number: There are 32 stations in each segment (without relays) as to 127
stations (with relays)
●
Contact pin: 9 frames D pin, the connector contact pins are as below:,
Contact pin of the connector
Instruction
1
-
Unused
2
-
Unused
3
B-Line
Positive data(twisted pair cables 1)
4
RTS
Sending requirement
5
GND_BUS
Isolation ground
6
+5V BUS
Isolated 5V DC power supply
7
-
Unused
8
A-Line
Negative data(twisted pair cables 2)
9
-
Unused
Housing
SHLD
PROFIBUS shielded cable
+5V and GND_BUS are used in the fieldbus terminals. Some devices, such as light
transceiver (RS485) may get external power supply form these pins.
RTS is used in some devices to determine the sending direction. Only A-Line wires, B-Line
wires and shield are used in the normal application.
It is recommended to apply the standard DB9 connector of SIEMENS. If the communication
baud rate is above 187.5kbps, please follow the connection rules of SIEMENS seriously.
Available Not available (with interference to the keypad wiring)
Summary of Contents for GD300-004G-4
Page 1: ...3...
Page 148: ...Goodrive300 inverters Basic operation instruction 147...
Page 159: ...Goodrive300 inverters Basic operation instruction 158...
Page 164: ...Goodrive300 inverters Basic operation instruction 163...
Page 173: ...Goodrive300 inverters Basic operation instruction 172...
Page 189: ...Goodrive300 inverters Basic operation instruction 188...
Page 204: ...Goodrive300 inverters Basic operation instruction 203...
Page 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Page 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Page 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...